Product Description
Specifications
Cells per unit 6
Nominal voltage 12
Terminal Type Front Access 5/16" Copper Insert
Capacity @ 77°F 225 AH (20 Hours)
(25°C) to 1.75v.p.c. 255 AH (100 Hours)
Short circuit current 9700 amps
Max discharge rate(1min rate) 854 amps
Impendance @ 77°F 25°C 1.42 milliohms
Electrolyte (S.G.) 1.300
CA (MCA) @ 32°F 2940
Reserve Capacity 25 amp 494
load to 10.5 volts
Ideal operating 68°F (20°C) to 77°F (25°C)
temperature range
Extended operating Discharge: -40°F to +140°F
Temperature range Charge: -60°F to +160°F
Float Voltage 2.25 to 2.3 Volts Per Cell
Cycle Service Voltage 2.33 to 2.36 Volts Per Cell
Max charging rate Cycle - 45 amps
Float - 37 amps
Discharge Rate to 3 hours - 60
1.75 Volts Per Cell 5 hours - 37
10 hours - 20.8
Weight lbs 178
Length x Width x Height case 21" x 8.5" x 8.88" (10.0")